MOD 30ML Functions
CONFIGURATION EXAMPLES
Figure 3. 19. Loaded ML_PID Compound
10. We will make the following changes to the loaded compound:
• Change the signal’s engineering range to 0-200.
• Change the display tag name to FIC-100 and the Engineering units to GPM
• Change the High alarm trip value to 150 and the low alarm trip value to 50 respectively.
The procedure is as given below:
• Select the VCI block and double-click on it to open the block. Type the high engineering units
and the high quality limits to 200. Select the Linearization type and change it to Square Root.
See the next figure for details:
3-13