MODCELL Multiloop Processor
ELECTRICAL CONNECTIONS
3.5.2 2004A SSR Input (DIM)
Make Solid-State Relay (SSR) connections as shown in Figure 3-4. These input modules
are used for sensing ON/OFF voltage levels. Each module provides optical isolation
between the field devices and the control logic. This isolation is limited to 250 Vrms at the
terminal block. Typical uses and applications for these input modules include sensing
voltage and contact conditions from: proximity switches, limit switches, selector switches,
push buttons, photoelectric switches, TTL compatible devices, float switches, or
thermostats.
Wire rating: 600 V, -20°C +105°C UL, CSA approved.
Input specifications are:
DIGITAL INPUTS (ISOLATED) _10__11__12_
Input voltage ranges 2.5-28Vdc 4-16Vdc 10-32Vdc, 12-32Vac
mA Input current at Max Line 30 45 25
Max Logic Low Input 1V, 0.2 mA 1V, 0.7 mA 3V, 1 mA
Input Resistance (Ohms) 900 300 1K (dc), 1.5K (ac)
Module Response Time (msec) 1.5 0.1 5
DIGITAL INPUTS (ISOLATED) _13__14__15_
Input voltage ranges 35-60Vac/dc 90-140Vac/dc 180-280Vac/dc
mA Input current at Max Line 6 (dc), 25 (ac) 11 7
Max Logic Low Input 9V, 0.8 mA 45V, 3 mA 80V, 1.7 mA
Input Resistance 10K Ohms 14K Ohms 43K Ohms
Module Response Time (msec) 10 (dc), 15 (ac) 20 20