Micromod RetroPAK: SLC Configuration Manual Manuale Utente Pagina 173

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 394
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 172
Command Series Migration to MOD 30ML
Pre-Configured – Cascade Control
To configure the inputs:
Open the AIN block AIN1 for input 1. See figure below:
Figure P5.2.
Cascade PID
You can change the Input Type and Linearization Type for the built-in input 1 here.
Specify the Input Signal Range also.
The VCI block ENG UNITS 1 in the loop compound is used for converting the voltage,
millivolts or current input signal to engineering units. See figure below:
Change the Linearization type (Linear, Square, Square root, Modified Square, Modifed
Square root) as required for the input signal and specify the Engineering Range and
Quality Limits.
P5- 5
Vedere la pagina 172
1 2 ... 168 169 170 171 172 173 174 175 176 177 178 ... 393 394

Commenti su questo manuale

Nessun commento